Protective relay system for the first demonstration of the HTS cable and the SFCL in live grid in Korea
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Lee, Seung Ryul | - |
dc.contributor.author | Yoon, Jaeyoung | - |
dc.contributor.author | Yang, Byeong-mo | - |
dc.contributor.author | Lee, Byongjun | - |
dc.date.accessioned | 2021-09-05T19:45:04Z | - |
dc.date.available | 2021-09-05T19:45:04Z | - |
dc.date.created | 2021-06-15 | - |
dc.date.issued | 2013-11 | - |
dc.identifier.issn | 0921-4534 | - |
dc.identifier.uri | https://scholar.korea.ac.kr/handle/2021.sw.korea/101767 | - |
dc.description.abstract | This study proposed a novel power protection system for the application of 22.9 kV HTS cable and SFCL systems to the Icheon substation in South Korea, and studied the protective coordination of the proposed system using a transient simulation program, PSCAD/EMTDC. Korea Electric Power Cooperation (KEPCO) designed and reconstructed the protection system of the Icheon substation based on the results of this study. The 22.9 kV, 50 MVA HTS cable and 22.9 kV, 630 A hybrid SFCL systems have been successfully operated in the live power grid of the Icheon substation since August, 2011. (C) 2013 Elsevier B.V. All rights reserved. | - |
dc.language | English | - |
dc.language.iso | en | - |
dc.publisher | ELSEVIER SCIENCE BV | - |
dc.title | Protective relay system for the first demonstration of the HTS cable and the SFCL in live grid in Korea | - |
dc.type | Article | - |
dc.contributor.affiliatedAuthor | Lee, Byongjun | - |
dc.identifier.doi | 10.1016/j.physc.2013.04.026 | - |
dc.identifier.scopusid | 2-s2.0-84884816949 | - |
dc.identifier.wosid | 000324688300068 | - |
dc.identifier.bibliographicCitation | PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, v.494, pp.286 - 291 | - |
dc.relation.isPartOf | PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS | - |
dc.citation.title | PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS | - |
dc.citation.volume | 494 | - |
dc.citation.startPage | 286 | - |
dc.citation.endPage | 291 | - |
dc.type.rims | ART | - |
dc.type.docType | Article | - |
dc.description.journalClass | 1 | - |
dc.description.journalRegisteredClass | scie | - |
dc.description.journalRegisteredClass | scopus | - |
dc.relation.journalResearchArea | Physics | - |
dc.relation.journalWebOfScienceCategory | Physics, Applied | - |
dc.relation.journalWebOfScienceCategory | Physics, Condensed Matter | - |
dc.subject.keywordAuthor | HTS cable | - |
dc.subject.keywordAuthor | SFCL | - |
dc.subject.keywordAuthor | Protection system | - |
dc.subject.keywordAuthor | Protective relay | - |
dc.subject.keywordAuthor | Power system | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
(02841) 서울특별시 성북구 안암로 14502-3290-1114
COPYRIGHT © 2021 Korea University. All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.