Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Optimal control of the gas-cooler pressure of a CO2 heat pump using EEV opening and outdoor fan speed in the cooling mode

Full metadata record
DC Field Value Language
dc.contributor.authorBaek, Changhyun-
dc.contributor.authorHeo, Jaehyeok-
dc.contributor.authorJung, Jongho-
dc.contributor.authorCho, Honghyun-
dc.contributor.authorKim, Yongchan-
dc.date.accessioned2021-09-06T00:58:23Z-
dc.date.available2021-09-06T00:58:23Z-
dc.date.created2021-06-18-
dc.date.issued2013-06-
dc.identifier.issn0140-7007-
dc.identifier.urihttps://scholar.korea.ac.kr/handle/2021.sw.korea/103053-
dc.description.abstractThe objective of this study is to investigate the control methods of the gas-cooler pressure in a CO2 heat pump. The cooling performance of the CO2 heat pump was measured by varying the refrigerant charge amount, EEV opening, compressor frequency, and outdoor fan speed at various outdoor temperatures. The effects of the EEV opening and the outdoor fan speed on the gas-cooler pressure and the COP were analyzed by using the experimental data. In the standard cooling condition at the compressor frequency of 45 Hz, the optimum gas-cooler pressure and the maximum COP were 9200 kPa and 3.04, respectively, at the optimum EEV opening of 41% and outdoor fan speed of 500 rpm. As the compressor frequency increased from 45 Hz to 55 Hz at the standard cooling condition, the optimum outdoor fan speed increased from 500 rpm to 700 rpm. (C) 2013 Elsevier Ltd and IIR. All rights reserved.-
dc.languageEnglish-
dc.language.isoen-
dc.publisherELSEVIER SCI LTD-
dc.subjectPERFORMANCE-
dc.titleOptimal control of the gas-cooler pressure of a CO2 heat pump using EEV opening and outdoor fan speed in the cooling mode-
dc.typeArticle-
dc.contributor.affiliatedAuthorKim, Yongchan-
dc.identifier.doi10.1016/j.ijrefrig.2013.02.009-
dc.identifier.scopusid2-s2.0-84877609178-
dc.identifier.wosid000319855500011-
dc.identifier.bibliographicCitationINTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, v.36, no.4, pp.1276 - 1284-
dc.relation.isPartOfINTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID-
dc.citation.titleINTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID-
dc.citation.volume36-
dc.citation.number4-
dc.citation.startPage1276-
dc.citation.endPage1284-
dc.type.rimsART-
dc.type.docTypeArticle-
dc.description.journalClass1-
dc.description.journalRegisteredClassscie-
dc.description.journalRegisteredClassscopus-
dc.relation.journalResearchAreaThermodynamics-
dc.relation.journalResearchAreaEngineering-
dc.relation.journalWebOfScienceCategoryThermodynamics-
dc.relation.journalWebOfScienceCategoryEngineering, Mechanical-
dc.subject.keywordPlusPERFORMANCE-
dc.subject.keywordAuthorCO2 heat pump-
dc.subject.keywordAuthorGas-cooler pressure-
dc.subject.keywordAuthorRefrigerant charge-
dc.subject.keywordAuthorElectronic expansion valve opening-
dc.subject.keywordAuthorOutdoor fan speed-
dc.subject.keywordAuthorCompressor frequency-
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > Department of Mechanical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher KIM, Yong Chan photo

KIM, Yong Chan
공과대학 (기계공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE