보일러 대수제어에 따른 사무소건물 난방에너지 절감에 대한 연구The Heating Energy Saving Effect by Operating Number Control of Boilers in Office Building
- Other Titles
- The Heating Energy Saving Effect by Operating Number Control of Boilers in Office Building
- Authors
- 윤갑천; 박두용; 윤경; 김영민; 김영섭; 김강수
- Issue Date
- 2013
- Publisher
- 한국건축친환경설비학회
- Keywords
- HW Boiler; Operating number control; Office; Heating energy; 보일러; 대수제어; 사무소; 난방에너지
- Citation
- 한국건축친환경설비학회 논문집, v.7, no.2, pp.120 - 125
- Indexed
- KCI
OTHER
- Journal Title
- 한국건축친환경설비학회 논문집
- Volume
- 7
- Number
- 2
- Start Page
- 120
- End Page
- 125
- URI
- https://scholar.korea.ac.kr/handle/2021.sw.korea/105127
- ISSN
- 1976-6483
- Abstract
- We proposed the operating number control of hot water boiler to save the heating energy consumption in office building. First,we split the existing boiler into two same capacity(500KW). As a result, the heating energy saving rate was 21%. And, we split the existing boiler into two capacity of 700KW and 300KW according to the heating load. In this case, the heating energy saving rate was 33%. These results presents the higher saving rates of heating energy consumption about 11% than that of the case of improving the existing boiler efficiency from 80% to 90%. Therefore, it can be said that the operating number control is more efficient way to reduce heating energy consumption than the improvement of existing boiler efficiency.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - College of Engineering > Department of Architecture > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.