Experimental Evaluation of Using the Surge PD Test as a Predictive Maintenance Tool for Monitoring Turn Insulation Quality in Random Wound AC Motor Stator Windings

Authors
Yang, JinkyuKang, Tae-juneKim, ByunghwanLee, Sang BinYoon, Young-WooKang, DongsikCho, JintaeKim, Heedong
Issue Date
2월-2012
Publisher
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
Keywords
AC machines; impulse testing; monitoring; partial discharges (PD); rotating machine insulation test; surges
Citation
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, v.19, no.1, pp.53 - 60
Indexed
SCIE
SCOPUS
Journal Title
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION
Volume
19
Number
1
Start Page
53
End Page
60
URI
https://scholar.korea.ac.kr/handle/2021.sw.korea/106109
DOI
10.1109/TDEI.2012.6148502
ISSN
1070-9878
Abstract
Turn insulation degradation is one of the major root causes of stator insulation failure leading to motor breakdown. The surge test is the only test available for testing the integrity of turn insulation; however, it is a high voltage pass/fail test that provides an indication only if an arc is instigated between the turns of weakened turn insulation, and therefore does not provide information regarding remaining lifetime. The surge PD test measures the partial discharge (PD) activity under surge excitation, and is used to date for assuring that voltage source PWM inverter-fed motors (IEC 60034-18-41 type I) are PD-free. In this paper, the potential of using the surge PD test as a predictive maintenance tool for turn insulation quality assessment is evaluated. Under the expectation that increasing PD activity in the voids formed by insulation degradation may be detectable before turn insulation failure, the test is performed periodically under accelerated thermal degradation on 6 windings. It is shown that change in the PD inception voltage under the surge PD test can be clearly observed before any other insulation test indicator. The results suggest that the surge PD test can be used for monitoring the condition of turn insulation for providing an early indication of stator insulation problems without the risk of puncturing turn insulation.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > School of Electrical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lee, Sang bin photo

Lee, Sang bin
공과대학 (전기전자공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE