Performance optimization of a hybrid ground source heat pump with the parallel configuration of a ground heat exchanger and a supplemental heat rejecter in the cooling mode
- Authors
- Park, Honghee; Lee, Joo Seoung; Kim, Wonuk; Kim, Yongchan
- Issue Date
- 9월-2012
- Publisher
- ELSEVIER SCI LTD
- Keywords
- Heat pump; Ground source; Optimization; Performance; COP; fFow rate
- Citation
- INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, v.35, no.6, pp.1537 - 1546
- Indexed
- SCIE
SCOPUS
- Journal Title
- INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID
- Volume
- 35
- Number
- 6
- Start Page
- 1537
- End Page
- 1546
- URI
- https://scholar.korea.ac.kr/handle/2021.sw.korea/107512
- DOI
- 10.1016/j.ijrefrig.2012.05.002
- ISSN
- 0140-7007
- Abstract
- A hybrid ground source heat pump (HGSHP) combining a ground flow loop and a supplemental heat rejecter loop in parallel is proposed to overcome the degradation of the ground thermal condition. The objective of this study is to optimize the performance of the HGSHP with the parallel configuration by varying the amount of refrigerant charge, the secondary fluid flow rate of the ground loop, and the secondary fluid flow rate of the supplemental loop. The coefficient of performance (COP) of the HGSHP with the parallel configuration was 21% higher than that of the conventional ground source heat pump (GSHP), and the heat rejection rate of the ground flow loop was 42% lower than that of the GSHP at the entering fluid temperature (EFT) of 40 degrees C in the ground heat exchanger and the EFT of 28 degrees C in the supplemental heat exchanger. (C) 2012 Elsevier Ltd and IIR. All rights reserved.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - College of Engineering > Department of Mechanical Engineering > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.