이산화탄소 급탕 열펌프의 운전조건에 따른 성능 특성에 관한 실험적 연구
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 손동진 | - |
dc.contributor.author | 백창현 | - |
dc.contributor.author | 허재혁 | - |
dc.contributor.author | 강훈 | - |
dc.contributor.author | 김용찬 | - |
dc.date.accessioned | 2021-09-07T20:08:30Z | - |
dc.date.available | 2021-09-07T20:08:30Z | - |
dc.date.created | 2021-06-17 | - |
dc.date.issued | 2011 | - |
dc.identifier.issn | 1229-6422 | - |
dc.identifier.uri | https://scholar.korea.ac.kr/handle/2021.sw.korea/114535 | - |
dc.description.abstract | In this study, the steady state performance of a CO_2 heat pump water heater was measured with a variation of operating conditions such as refrigerant charge amount, compressor frequency, EEV opening, and water mass flow rate. Transient state performance tests were also conducted to investigate major system effects associated with the interaction between the CO_2 heat pump water heater and the water tank. Optimum refrigerant charge amount for the system was 1600 g. At compressor frequencies of 50 Hz and 60 Hz, water mass flow rates of 95 kg/h and 105 kg/h, and EEV opening of 8% and 16%, the water heating temperatures were 65℃ and 68℃ and COPs were 3.0 and 2.8, respectively. In the transient condition, the instantaneous COP decreased with an increase in the inlet water temperature. | - |
dc.language | Korean | - |
dc.language.iso | ko | - |
dc.publisher | 대한설비공학회 | - |
dc.title | 이산화탄소 급탕 열펌프의 운전조건에 따른 성능 특성에 관한 실험적 연구 | - |
dc.title.alternative | Experimental Study on the Performance of a CO_2 Heat Pump Water Heater under Various Operating Conditions | - |
dc.type | Article | - |
dc.contributor.affiliatedAuthor | 김용찬 | - |
dc.identifier.bibliographicCitation | 설비공학 논문집, v.23, no.4, pp.273 - 280 | - |
dc.relation.isPartOf | 설비공학 논문집 | - |
dc.citation.title | 설비공학 논문집 | - |
dc.citation.volume | 23 | - |
dc.citation.number | 4 | - |
dc.citation.startPage | 273 | - |
dc.citation.endPage | 280 | - |
dc.type.rims | ART | - |
dc.identifier.kciid | ART001544654 | - |
dc.description.journalClass | 2 | - |
dc.description.journalRegisteredClass | kci | - |
dc.subject.keywordAuthor | CO_2 heat pump water heater(이산화탄소 급탕 열펌프) | - |
dc.subject.keywordAuthor | Water heating temperature (급탕온도) | - |
dc.subject.keywordAuthor | Coefficient of Performance(COP | - |
dc.subject.keywordAuthor | 성능계수) | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
(02841) 서울특별시 성북구 안암로 14502-3290-1114
COPYRIGHT © 2021 Korea University. All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.