PERFORMANCE CHARACTERISTICS OF A SIMULTANEOUS HEATING AND COOLING HEAT PUMP IN THE HEAT RECOVERY MODE
DC Field | Value | Language |
---|---|---|
dc.contributor.author | JONGMIN CHOI | - |
dc.contributor.author | HYUN JOON CHOUNG | - |
dc.contributor.author | YOUNGJU JOO | - |
dc.contributor.author | HOON KANG | - |
dc.contributor.author | 김용찬 | - |
dc.date.accessioned | 2021-09-08T08:52:30Z | - |
dc.date.available | 2021-09-08T08:52:30Z | - |
dc.date.created | 2021-06-17 | - |
dc.date.issued | 2010 | - |
dc.identifier.issn | 2010-1325 | - |
dc.identifier.uri | https://scholar.korea.ac.kr/handle/2021.sw.korea/118192 | - |
dc.description.abstract | The cooling load in winter is significant in buildings and hotels because of the usage of office equipments and the high efficiency of wall insulation. Hence, the development of a multi-heat pump that can cover heating and cooling simultaneously for each indoor unit is required. In this study, the performance of a simultaneous heating and cooling heat pump was investigated in the heat recovery mode (HR mode). The system adopted a variable speed compressor using R-410A with four indoor units and one outdoor unit. In the HR mode, the capacity and COP were improved as compared with those in the cooling or heating mode because the waste heat in the outdoor unit was utilized as useful heat in the indoor units. However, energy imbalance between heating and cooling capacities of each indoor unit was observed in the 2H–1C HR mode. Therefore, the performance of the system in the 2H–1C HR mode was enhanced by controlling refrigerant flow rate through the outdoor unit. | - |
dc.language | English | - |
dc.language.iso | en | - |
dc.publisher | 대한설비공학회 | - |
dc.title | PERFORMANCE CHARACTERISTICS OF A SIMULTANEOUS HEATING AND COOLING HEAT PUMP IN THE HEAT RECOVERY MODE | - |
dc.title.alternative | PERFORMANCE CHARACTERISTICS OF A SIMULTANEOUS HEATING AND COOLING HEAT PUMP IN THE HEAT RECOVERY MODE | - |
dc.type | Article | - |
dc.contributor.affiliatedAuthor | 김용찬 | - |
dc.identifier.bibliographicCitation | International Journal of Air-Conditioning and Refrigeration, v.18, no.3, pp.237 - 245 | - |
dc.relation.isPartOf | International Journal of Air-Conditioning and Refrigeration | - |
dc.citation.title | International Journal of Air-Conditioning and Refrigeration | - |
dc.citation.volume | 18 | - |
dc.citation.number | 3 | - |
dc.citation.startPage | 237 | - |
dc.citation.endPage | 245 | - |
dc.type.rims | ART | - |
dc.identifier.kciid | ART001518545 | - |
dc.description.journalClass | 2 | - |
dc.description.journalRegisteredClass | kci | - |
dc.subject.keywordAuthor | Simultaneous heating and cooling | - |
dc.subject.keywordAuthor | heat pump | - |
dc.subject.keywordAuthor | heat recovery | - |
dc.subject.keywordAuthor | COP | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
(02841) 서울특별시 성북구 안암로 14502-3290-1114
COPYRIGHT © 2021 Korea University. All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.