Performance characteristics of a MPCM slurry cooled unit designed for telecommunication equipment

Full metadata record
DC Field Value Language
dc.contributor.authorChoi, Jongmin-
dc.contributor.authorJeon, Jongug-
dc.contributor.authorKim, Yongchan-
dc.date.accessioned2021-09-09T10:44:43Z-
dc.date.available2021-09-09T10:44:43Z-
dc.date.created2021-06-10-
dc.date.issued2008-03-
dc.identifier.issn1738-494X-
dc.identifier.urihttps://scholar.korea.ac.kr/handle/2021.sw.korea/123977-
dc.description.abstractOptimum control of the PCB surface temperature is very important in achieving high performance and operational reliability of telecommunication equipment with high power density and thermal density. In this study, the performance of a liquid cooling unit with MPCM slurries (called as "MPCM cooled unit") was tested and analyzed. In addition, its performance was compared with that of an air cooled unit and a water cooled unit. The maximum Surface temperature and the index of uniform temperature distribution (IUTD) were introduced to analyze cooling performance. The surface temperature in the unit rack of telecommunication equipment can be controlled properly by using an MPCM cooled unit instead of an air cooled unit. The maximum surface temperature and IUTD of the MPCM cooled unit at the inlet temperature of 19 degrees C were lower than those at inlet temperatures of 25 degrees C and 27 degrees C due to the increases of heat capacity and heat transfer rate. The heat capacity of the MPCM cooled unit increased significantly with the increase of mass flow rate due to high specific heat of MPCM particles with latent heat transfer rate. The cooling performance of the MPCM cooled unit was superior to that of the water cooled unit.-
dc.languageEnglish-
dc.language.isoen-
dc.publisherKOREAN SOC MECHANICAL ENGINEERS-
dc.subjectHEAT-
dc.subjectFLOW-
dc.titlePerformance characteristics of a MPCM slurry cooled unit designed for telecommunication equipment-
dc.typeArticle-
dc.contributor.affiliatedAuthorKim, Yongchan-
dc.identifier.doi10.1007/s12206-007-1212-5-
dc.identifier.scopusid2-s2.0-49249136828-
dc.identifier.wosid000254145300019-
dc.identifier.bibliographicCitationJOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, v.22, no.3, pp.575 - 582-
dc.relation.isPartOfJOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY-
dc.citation.titleJOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY-
dc.citation.volume22-
dc.citation.number3-
dc.citation.startPage575-
dc.citation.endPage582-
dc.type.rimsART-
dc.type.docTypeArticle-
dc.identifier.kciidART001222316-
dc.description.journalClass1-
dc.description.journalRegisteredClassscie-
dc.description.journalRegisteredClassscopus-
dc.description.journalRegisteredClasskci-
dc.relation.journalResearchAreaEngineering-
dc.relation.journalWebOfScienceCategoryEngineering, Mechanical-
dc.subject.keywordPlusHEAT-
dc.subject.keywordPlusFLOW-
dc.subject.keywordAuthorMPCM-
dc.subject.keywordAuthorliquid cooling-
dc.subject.keywordAuthorheat density-
dc.subject.keywordAuthortelecommunication equipment-
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > Department of Mechanical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher KIM, Yong Chan photo

KIM, Yong Chan
공과대학 (기계공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE