하천수 열원 이용 2단압축 열펌프의 최적성능 및효용 운전범위에 관한 시뮬레이션 연구Simulation on the Optimal Performance and Effective Operating Rangeof a 2-Stage Compression Heat Pump Using River Water
- Other Titles
- Simulation on the Optimal Performance and Effective Operating Rangeof a 2-Stage Compression Heat Pump Using River Water
- Authors
- 정태훈; 박차식; 김용찬
- Issue Date
- 2008
- Publisher
- 대한설비공학회
- Keywords
- River water(하천수); 2-stage compression heat pump(2단압축 열펌프); Electronic expansion valve(EEV; 전자팽창장치); Simulation(시뮬레이션)
- Citation
- 설비공학 논문집, v.20, no.5, pp.295 - 303
- Indexed
- KCI
- Journal Title
- 설비공학 논문집
- Volume
- 20
- Number
- 5
- Start Page
- 295
- End Page
- 303
- URI
- https://scholar.korea.ac.kr/handle/2021.sw.korea/124732
- ISSN
- 1229-6422
- Abstract
- The objectives of this study are to predict actual system performance and effective operating range of the 2-stage compression heat pump system using river water. An electronic expansion valve was applied to the simulation to analyze the effects of operating conditions on the system performance. The developed program was verified by comparing the predictions with the measured data. The results from the present model showed a good agreement with the measured data. In addition, the heat pump simulation was conducted by increasing condenser reservoir inlet temperature to investigate the benefits of the 2-stage compression over the 1-stage compression in the heating mode. The performance of the 2- stage compression cycle was better than that of the 1-stage compression when the inlet temperature of the condenser reservoir was higher than 40℃.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - College of Engineering > Department of Mechanical Engineering > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.