Influences of different operational configurations on combined effects of room air stratification and thermal decay in UFAD system
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 이광호 | - |
dc.date.accessioned | 2022-04-09T05:40:21Z | - |
dc.date.available | 2022-04-09T05:40:21Z | - |
dc.date.created | 2022-04-08 | - |
dc.date.issued | 2018-10 | - |
dc.identifier.issn | 0378-7788 | - |
dc.identifier.uri | https://scholar.korea.ac.kr/handle/2021.sw.korea/139725 | - |
dc.description.abstract | The non-insulated underfloor supply plenum and the heat gain of the cool supply air into supply plenum results in significant magnitude of thermal decay defined as the supply air temperature rise. Eventually, these changes have influence on the room air stratification, causing negative effects throughout whole system. Therefore, for the optimization of UFAD system, it is important to understand these fundamentals and relevant effects on the overall system operation. In this study, comparative analysis was conducted during cooling period using validated EnergyPlus model, after employing different operational configurations related to room air stratification and thermal decay. The thermal behavior and cooling energy performance were analyzed by observing the convective heat transfer, thermal decay, airflow, stratification among different operational configurations. As a result, it was observed that the existence of non-insulated supply plenum have influences on the thermal behavior in occupied zone, and the corresponding heat transfer has load reduction effect of the space by about 40%. However, there were still significant amounts of cooling energy consumption in the form of thermal decay despite the reduced cooling load, indicating that unintended and additional energy consumptio | - |
dc.language | English | - |
dc.language.iso | en | - |
dc.publisher | ELSEVIER SCIENCE SA | - |
dc.title | Influences of different operational configurations on combined effects of room air stratification and thermal decay in UFAD system | - |
dc.type | Article | - |
dc.contributor.affiliatedAuthor | 이광호 | - |
dc.identifier.doi | 10.1016/j.enbuild.2018.07.015 | - |
dc.identifier.bibliographicCitation | ENERGY AND BUILDINGS, v.176, pp.262 - 274 | - |
dc.relation.isPartOf | ENERGY AND BUILDINGS | - |
dc.citation.title | ENERGY AND BUILDINGS | - |
dc.citation.volume | 176 | - |
dc.citation.startPage | 262 | - |
dc.citation.endPage | 274 | - |
dc.type.rims | ART | - |
dc.type.docType | Article | - |
dc.description.journalClass | 1 | - |
dc.description.journalRegisteredClass | scie | - |
dc.description.journalRegisteredClass | scopus | - |
dc.subject.keywordAuthor | Energy modeling | - |
dc.subject.keywordAuthor | EnergyPlus | - |
dc.subject.keywordAuthor | Room air stratification | - |
dc.subject.keywordAuthor | Thermal decay | - |
dc.subject.keywordAuthor | Underfloor air distribution | - |
dc.subject.keywordAuthor | Underfloor supply plenum | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
(02841) 서울특별시 성북구 안암로 14502-3290-1114
COPYRIGHT © 2021 Korea University. All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.