Analysis of thermal environment and energy performance by biased economizer outdoor air temperature sensor fault
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Kim, Chul Ho | - |
dc.contributor.author | Lee, Sung Chan | - |
dc.contributor.author | Park, Kyung Soon | - |
dc.contributor.author | Lee, Kwang Ho | - |
dc.date.accessioned | 2022-12-09T21:41:57Z | - |
dc.date.available | 2022-12-09T21:41:57Z | - |
dc.date.created | 2022-12-08 | - |
dc.date.issued | 2022-04 | - |
dc.identifier.issn | 1738-494X | - |
dc.identifier.uri | https://scholar.korea.ac.kr/handle/2021.sw.korea/146648 | - |
dc.description.abstract | In order to develop a fault detection and diagnosis (FDD) algorithm for air handling unit (AHU) based on machine learning, the economizer outdodor air temperature (OAT) sensor fault was modeled. Through EnergyPlus program, the economizer OAT sensor modeled a fault that measures the OAT that's higher or lower than the actual temperature. The distribution of abnormal node point air temperature produced by the fault at the control point of the economizer was reviewed. In addition, the relationship between OAT & mixed air temperature (MAT), OAT & outdoor air fraction (OAF), AHU cooling coil energy, and chiller energy were comparatively analyzed for each fault model. In the case of the fault models, although outdoor air suitable for cooling could be utilized during the operation, outdoor air was not introduced for cooling, and in the opposite case, outdoor air was introduced even when OAT was higher than the indoor set-point temperature, reducing the energy saving effect for cooling. In the future, we aim to analyze energy performance and indoor air quality according to the fault in the return air temperature (RAT) sensor and error in the opening position of the damper. In addition, we plan to continue the analysis of fault data for the various elements of an AHU, and develop FDD algorithms using machine learning. | - |
dc.language | English | - |
dc.language.iso | en | - |
dc.publisher | KOREAN SOC MECHANICAL ENGINEERS | - |
dc.title | Analysis of thermal environment and energy performance by biased economizer outdoor air temperature sensor fault | - |
dc.type | Article | - |
dc.contributor.affiliatedAuthor | Kim, Chul Ho | - |
dc.identifier.doi | 10.1007/s12206-022-0342-0 | - |
dc.identifier.scopusid | 2-s2.0-85127425937 | - |
dc.identifier.wosid | 000775893100017 | - |
dc.identifier.bibliographicCitation | JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, v.36, no.4, pp.2083 - 2094 | - |
dc.relation.isPartOf | JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY | - |
dc.citation.title | JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY | - |
dc.citation.volume | 36 | - |
dc.citation.number | 4 | - |
dc.citation.startPage | 2083 | - |
dc.citation.endPage | 2094 | - |
dc.type.rims | ART | - |
dc.type.docType | Article | - |
dc.identifier.kciid | ART002830924 | - |
dc.description.journalClass | 1 | - |
dc.description.journalRegisteredClass | scie | - |
dc.description.journalRegisteredClass | scopus | - |
dc.description.journalRegisteredClass | kci | - |
dc.relation.journalResearchArea | Engineering | - |
dc.relation.journalWebOfScienceCategory | Engineering, Mechanical | - |
dc.subject.keywordAuthor | Economizer | - |
dc.subject.keywordAuthor | Fault detection diagnosis | - |
dc.subject.keywordAuthor | Machine learning | - |
dc.subject.keywordAuthor | EnergyPlus | - |
dc.subject.keywordAuthor | Outdoor air temperature sensor | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
(02841) 서울특별시 성북구 안암로 14502-3290-1114
COPYRIGHT © 2021 Korea University. All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.