Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

VRF 시스템 적용 건물의 온도 및 쾌적 제어에 따른 에너지 성능과 실내 열쾌적 비교 분석

Full metadata record
DC Field Value Language
dc.contributor.author김철호-
dc.contributor.author전종욱-
dc.contributor.author이승언-
dc.contributor.author김강수-
dc.date.accessioned2021-09-03T13:57:38Z-
dc.date.available2021-09-03T13:57:38Z-
dc.date.created2021-06-17-
dc.date.issued2017-
dc.identifier.issn1226-9107-
dc.identifier.urihttps://scholar.korea.ac.kr/handle/2021.sw.korea/86044-
dc.description.abstractEven though the building temperature setting guideline saves energy, it does not take the occupants' thermal comfort into consideration. In this study, we selected a college building equipped with VRF system, and created a simulation model using EnergyPlus similar to the actual building to compare and analyze actual energy usage. We evaluated thermal comfort index and energy performance output based on temperature and thermal comfort control method after we verified the validity of the model. When the buildings' actual energy usage and simulation results were compared, MBE was 4.62% and Cv(RMSE) was 7.86%. The MBE and Cv(RMSE) values satisfied ASHRAE standards. When the temperature was adjusted to 24℃, the thermal comfort ratio was approximately 41%. When comfort control was carried out with PMV 0.5, thermal comfort ratio was increased to approximately 92% by executing cooling, dehumidification, and blowing modes. The comfort control model case showed 5.1% increase in energy consumption compared to the base case. However, 7.4% energy was saved when the temperature was controlled at 24℃ assumed to similar condition like PMV 0.5 comfort control. Therefore, evaluation showed that thermal comfort control allows better energy saving as well as increased thermal comfort than performing simple temperature control method.-
dc.languageKorean-
dc.language.isoko-
dc.publisher대한건축학회-
dc.titleVRF 시스템 적용 건물의 온도 및 쾌적 제어에 따른 에너지 성능과 실내 열쾌적 비교 분석-
dc.title.alternativeComparison of Energy Performance and Indoor Thermal Comfort according to Temperature and Comfort Control in VRF System-
dc.typeArticle-
dc.contributor.affiliatedAuthor김강수-
dc.identifier.doi10.5659/JAIK_SC.2017.33.11.53-
dc.identifier.bibliographicCitation대한건축학회논문집 구조계, v.33, no.11, pp.53 - 61-
dc.relation.isPartOf대한건축학회논문집 구조계-
dc.citation.title대한건축학회논문집 구조계-
dc.citation.volume33-
dc.citation.number11-
dc.citation.startPage53-
dc.citation.endPage61-
dc.type.rimsART-
dc.identifier.kciidART002285557-
dc.description.journalClass2-
dc.description.journalRegisteredClasskci-
dc.subject.keywordAuthorVRF(Variable Refringent Flow) Heat Pump-
dc.subject.keywordAuthorPerformance Curve-
dc.subject.keywordAuthorTemperature Control-
dc.subject.keywordAuthorThermal Comfort Control-
dc.subject.keywordAuthorEnergyPlus-
dc.subject.keywordAuthor냉매 유량 가변형 히트펌프-
dc.subject.keywordAuthor성능 곡선-
dc.subject.keywordAuthor온도 제어-
dc.subject.keywordAuthor쾌적 제어-
dc.subject.keywordAuthor에너지플러스-