Air side heat transfer coefficients of discrete plate finned-tube heat exchangers with large fin pitch

Citations

WEB OF SCIENCE

48
Citations

SCOPUS

60

초록

The objective of this study is to investigate the heat transfer characteristics of discrete plate finned-tube heat exchangers with large fin pitches. Thirty-four heat exchangers were tested with variations of fin pitches, the number of tube rows, fin alignment, and vertical fin space. The j-factor of the discrete plate finned-tube exchanger was analyzed as a function of coil geometry and then compared with that of the continuous plate finned-tube heat exchanger. For fin pitches of 7.5-15 mm, the j-factors; of the discrete plate finned-tube heat exchangers were 6.0-11.6% higher than those of the continuous plate finned-tube heat exchangers. Two separate correlations for the j-factor were developed for the inline and the staggered fin alignment in the discrete plate finned-tube heat exchangers to predict the measured data within a relative deviation of 2.9%. (C) 2009 Elsevier Ltd. All rights reserved.

키워드

Plate heat exchangersDiscrete finLarge fin pitchFin alignmentFRICTION CHARACTERISTICS
제목
Air side heat transfer coefficients of discrete plate finned-tube heat exchangers with large fin pitch
저자
Choi, Jong MinKim, YonghanLee, MooyeonKim, Yongchan
DOI
10.1016/j.applthermaleng.2009.08.001
발행일
2010-02
유형
Article
저널명
Applied Thermal Engineering
30
2-3
페이지
174 ~ 180