난방주체 운전모드에서의 동시냉난방 열펌프 성능향상에 관한 실험적 연구

Experimental Study on the Performance Improvement of a Simultaneous Heating and Cooling Heat Pump in the Heating-main Operating Mode

초록

The cooling load in winter is significant in buildings and hotels because of the usage of office equipments and the high efficiency of wall insulation. Hence, the development of a multi-heat pump that can cover heating and cooling simultaneously for each indoor unit is required. In this study, the operating characteristics and performance of a simultaneous heating and cooling heat pump in the heating-main operating mode were investigated experimentally. The system adopted a variable speed compressor with four indoor units and one outdoor unit with R-410A. In the heating-main mode, the cooling capacity was lower than the design cooling capacity due to the reduction of the flow rate in the indoor unit for the cooling, with the increase of the heating capacity. To solve these problems, the performance characteristics of the simultaneous heating and cooling heat pump in the heating-main mode were investigated by varying the flow rate to the indoor unit for the cooling and the compressor rotating speed. In addition, the adequate control methods were suggested to improve the system efficiency.

키워드

Simultaneous heating and cooling(동시냉난방)Heat pump(열펌프)Heat recovery (열회수)Operating mode(운전모드)
제목
난방주체 운전모드에서의 동시냉난방 열펌프 성능향상에 관한 실험적 연구
제목 (타언어)
Experimental Study on the Performance Improvement of a Simultaneous Heating and Cooling Heat Pump in the Heating-main Operating Mode
저자
강훈정현준주영주김용찬최종민
발행일
2008
저널명
설비공학 논문집
20
4
페이지
245 ~ 251