System-Level Vulnerability Analysis for Commutation Failure Mitigation in Multi-infeed HVDC Systems

Citations

WEB OF SCIENCE

7
Citations

SCOPUS

8

초록

This paper deals with commutation failure of the line-commutated converter high voltage direct current (LCC HVDC) system caused by a three phase fault in the ac power system. An analytic calculation method is proposed to estimate the maximum permissible voltage drop at the LCC HVDC station on various operating point and to assess the area of vulnerability for commutation failure (AOV-CF) in the power system based on the residual phase voltage equation. The concept is extended to multi-infeed HVDC power system as the area of severity for simultaneous commutation failure (AOS-CF). In addition, this paper presents the implementation of a shunt compensator applying to the proposed method. An analysis and simulation have been performed with the IEEE 57 bus sample power system and the Jeju island power system in Korea.

키워드

HVDCMulti-infeedLCCCommutation failurePower systemTRANSMISSION-SYSTEMSVOLTAGESEVERITYAREA
제목
System-Level Vulnerability Analysis for Commutation Failure Mitigation in Multi-infeed HVDC Systems
저자
Yoon, MinhanJang, Gilsoo
DOI
10.5370/JEET.2018.13.3.1052
발행일
2018-05
유형
Article
저널명
Journal of Electrical Engineering & Technology
13
3
페이지
1052 ~ 1059