Implementation of superconducting fault current limiter for flexible operation in the power substation
- Song, Chong Suk;
- Lee, Hansang;
- Cho, Yoon-sung;
- Suh, Jaewan;
- Jang, Gilsoo
WEB OF SCIENCE
3초록
The concentration of large-scale power loads located in the metropolitan areas have resulted in high fault current levels during a fault thereby requiring the substation to operate in the double busbar configuration mode. However, the double busbar configuration mode results in deterioration of power system reliability and unbalanced power flow in the adjacent transmission lines which may result in issues such as overloading of lines. This paper proposes the implementation of the superconducting fault current limiter (SFCL) to be installed between the two substation busbars for a more efficient and flexible operation of the substation enabling both single and double busbar configurations depending on the system conditions for guaranteeing power system reliability as well as fault current limitations. Case studies are being performed for the effectiveness of the SFCL installation and results are compared for the cases where the substation is operating in single and double busbar mode and with and without the installation of the SFCL for fault current mitigation. (C) 2014 Elsevier B.V. All rights reserved.