상세 보기
Performance evaluation of a two-stage CO2 cycle with gas injection in the cooling mode operation
- Cho, Honghyun;
- Baek, Changhyun;
- Park, Chasik;
- Kim, Yongchan
WEB OF SCIENCE
72SCOPUS
70초록
The cooling performance and reliability of a transcritical CO2 cycle can be significantly improved by using a multi-stage compressor with gas injection because the CO2 cycle has a large pressure difference across a compressor. The objective of this study is to investigate the performance and operating characteristics of a two-stage CO2 cycle with gas injection. in this study, the performances of a two-stage CO2 cycle with gas injection (called as "two-stage gas injection cycle") were measured as the amount of refrigerant charge, first- and second-stage compressor frequencies, and first- and second-stage EEV openings were varied in the cooling mode operation. The cooling COP of the two-stage gas injection cycle was maximally enhanced by 16.5% over that of the two-stage non-injection cycle in the experiments. In addition, when the first- and second-stage EEV openings were increased, the compression ratio decreased and this in turn, improved the cooling COP of the two-stage gas injection cycle. However, when the first-stage EEV opening was increased, the mass flow rate through the evaporator decreased, and this in turn, decreased the cooling capacity of the two-stage gas injection cycle. Therefore, in the two-stage gas injection cycle, an optimum control of both EEV openings is required. (C) 2008 Elsevier Ltd and IIR. All rights reserved.
키워드
- 제목
- Performance evaluation of a two-stage CO2 cycle with gas injection in the cooling mode operation
- 저자
- Cho, Honghyun; Baek, Changhyun; Park, Chasik; Kim, Yongchan
- 발행일
- 2009-01
- 유형
- Article
- 권
- 32
- 호
- 1
- 페이지
- 40 ~ 46