상세 보기
Saturation Detection-Based Blocking Scheme for Transformer Differential Protection
- Lee, Byung Eun;
- Lee, Jinsik;
- Won, Sung Ho;
- Lee, Byongjun;
- Crossley, Peter A.;
- 외 1명
WEB OF SCIENCE
4SCOPUS
6초록
This paper describes a current differential relay for transformer protection that operates in conjunction with a core saturation detection-based blocking algorithm. The differential current for the magnetic inrush or over-excitation has a point of inflection at the start and end of each saturation period of the transformer core. At these instants, discontinuities arise in the first-difference function of the differential current. The second-and third-difference functions convert the points of inflection into pulses, the magnitudes of which are large enough to detect core saturation. The blocking signal is activated if the third-difference of the differential current is larger than the threshold and is maintained for one cycle. In addition, a method to discriminate between transformer saturation and current transformer (CT) saturation is included. The performance of the proposed blocking scheme was compared with that of a conventional harmonic blocking method. The test results indicate that the proposed scheme successfully discriminates internal faults even with CT saturation from the magnetic inrush, over-excitation, and external faults with CT saturation, and can significantly reduce the operating time delay of the relay.
키워드
- 제목
- Saturation Detection-Based Blocking Scheme for Transformer Differential Protection
- 저자
- Lee, Byung Eun; Lee, Jinsik; Won, Sung Ho; Lee, Byongjun; Crossley, Peter A.; Kang, Yong Cheol
- 발행일
- 2014-07
- 유형
- Article
- 저널명
- Energies
- 권
- 7
- 호
- 7
- 페이지
- 4571 ~ 4587
- 언어
- ENG
- 출판사
- MDPI AG
- 발행국가
- 스위스
- 분량
- 17 페이지
- ISSN
- P 1996-1073