This paper describes a current differential relay for transformer protection that operates in conjunction with a core saturation detection-based blocking algorithm. The differential current for the magnetic inrush or over-excitation has a point of inflection at the start and end of each saturation period of the transformer core. At these instants, discontinuities arise in the first-difference function of the differential current. The second-and third-difference functions convert the points of inflection into pulses, the magnitudes of which are large enough to detect core saturation. The blocking signal is activated if the third-difference of the differential current is larger than the threshold and is maintained for one cycle. In addition, a method to discriminate between transformer saturation and current transformer (CT) saturation is included. The performance of the proposed blocking scheme was compared with that of a conventional harmonic blocking method. The test results indicate that the proposed scheme successfully discriminates internal faults even with CT saturation from the magnetic inrush, over-excitation, and external faults with CT saturation, and can significantly reduce the operating time delay of the relay.

키워드

saturation detection based blocking; harmonic blocking; current differential relay; transformer protection; operating time delay; 3-PHASE POWER TRANSFORMERS; ALGORITHM; COMPUTER; FAULT; RELAY
제목
Saturation Detection-Based Blocking Scheme for Transformer Differential Protection
저자
Lee, Byung Eun; Lee, Jinsik; Won, Sung Ho; Lee, Byongjun; Crossley, Peter A.; Kang, Yong Cheol
DOI
10.3390/en7074571
발행일
2014-07
유형
Article
저널명
Energies
권
7
호
7
페이지
4571 ~ 4587