상세 보기
Unsteady RANS modeling of water-spray suppression for large-scale compartment pool fires
- Yoon, Sam S.;
- Kim, Ho Young;
- DesJardin, Paul E.;
- Hewson, John C.;
- Tieszen, Sheldon R.;
- 외 1명
WEB OF SCIENCE
6SCOPUS
5초록
This paper presents a computational study of the effect of water-spray characteristics on the suppression of a large-scale (2 m x 2 m) JP-8 pool fire in a 10 m x 10 m x 10 m compartment with an open ceiling. The numerical model is based on an unsteady Reynolds-averaged Navier-Stokes formulation using a stochastic separated flow approach for the droplets that includes detailed descriptions of the interaction between water droplets and fire plume. Simulation results indicate that water-spray injection causes the gas temperature to rise due to the initial enhancement of the turbulent mixing. A threshold suppression condition is achieved when the injected droplet carries enough momentum (injection speed range is 20-80 m/s) to penetrate the fire plume and evaporate in the flame regions where most of the gas-phase combustion is taking place. In addition, the droplet size (ranging from 100-800 mu m) should be small enough to yield quick evaporation when in contact with the flame surface for efficient cooling. Based on a parametric study, a preferred fire suppression configuration is recommended for the systems considered.
키워드
- 제목
- Unsteady RANS modeling of water-spray suppression for large-scale compartment pool fires
- 저자
- Yoon, Sam S.; Kim, Ho Young; DesJardin, Paul E.; Hewson, John C.; Tieszen, Sheldon R.; Blanchat, Thomas K.
- 발행일
- 2007
- 유형
- Article
- 권
- 17
- 호
- 1
- 페이지
- 1 ~ 45