Composite fouling characteristics of CaCO3 and CaSO4 in plate heat exchangers at various operating and geometric conditions

  • Song, Kang Sub
  • Lim, Junyub
  • Yun, Sungho
  • Kim, Dongwoo
  • Kim, Yongchan
Citations

WEB OF SCIENCE

56
Citations

SCOPUS

63

초록

In a water heating system, such as a district heating and hot water supply system, the composite fouling of CaCO3 and CaSO4 characterizes the actual usage environment. In this study, the composite fouling characteristics of CaCO3 and CaSO4 in plate heat exchangers were measured and analyzed at various concentrations, flow velocities, temperatures, and chevron angles. Moreover, based on the measured data, empirical correlations for the fouling resistance, fouling period, and pressure drop ratio at an asymptotic state, are developed as a function of concentration, Re, temperature, and chevron angle. The correlations for the fouling resistance, fouling period, and pressure drop ratio at the asymptotic state yield satisfactory predictions with mean absolute errors of 7.1%, 4.6%, and 2.0%, respectively. In addition, the sensitivities of the operating and geometrical parameters on the composite fouling characteristics are analyzed using modified regression coefficients. (C) 2019 Elsevier Ltd. All rights reserved.

키워드

Composite fouling (CaCO3/CaSO4)Plate heat exchangerAsymptotic fouling resistanceAsymptotic fouling periodAsymptotic pressure drop ratioCALCIUM-SULFATETHERMAL-RESISTANCEMODELPERFORMANCECARBONATE
제목
Composite fouling characteristics of CaCO3 and CaSO4 in plate heat exchangers at various operating and geometric conditions
저자
Song, Kang SubLim, JunyubYun, SunghoKim, DongwooKim, Yongchan
DOI
10.1016/j.ijheatmasstransfer.2019.03.032
발행일
2019-06
유형
Article
저널명
International Journal of Heat and Mass Transfer
136
페이지
555 ~ 562