Chilled water temperature set-point reset based on outdoor air temperature and its cooling energy performance in an office building

  • Lee, Young Jun
  • Hong, Sung Hyup
  • Lee, Jong Man
  • Yoon, Yeo Beom
  • Choi, Jong Min
  • ... Lee, Kwang Ho
Citations

WEB OF SCIENCE

8
Citations

SCOPUS

8

초록

In this study, the cooling energy performance of two strategies for controlling ChWT (chilled water temperature) are compared: the conventional control strategy of constantly fixing ChWT and the OAT (outdoor air temperature) compensation control strategy that adjusts ChWT according to the changes in OAT. OAT compensation control strategy was modeled and realized based on Appendix G of ASHRAE Standard 90.1. It was confirmed that applying OAT compensation control strategy can significantly reduce chiller energy consumption, which accounts for the largest portion of total cooling energy consumption. It was found that the difference in total cooling energy consumption between applying the conventional control of constantly fixing ChWT to 6 degrees C and applying the OAT compensation control was approximately 8 % and 3 % during spring (March to May) and summer (June to August), respectively. Additionally, during the fall (September-November) period, about 7 % of total cooling energy consumption could be saved.

키워드

AHU (air handling unit)Chilled water temperature set-pointCooling energyOutdoor air temperature compensation controlVAV (variable air volume)ARTIFICIAL NEURAL-NETWORKSOPTIMIZATIONSTRATEGYSYSTEMSVRF
제목
Chilled water temperature set-point reset based on outdoor air temperature and its cooling energy performance in an office building
저자
Lee, Young JunHong, Sung HyupLee, Jong ManYoon, Yeo BeomChoi, Jong MinLee, Kwang Ho
DOI
10.1007/s12206-022-0241-4
발행일
2022-03
유형
Article
저널명
Journal of Mechanical Science and Technology
36
3
페이지
1557 ~ 1568