Control Strategy for Line Overload and Short Circuit Current of Networked Distribution Systems

Citations

WEB OF SCIENCE

4
Citations

SCOPUS

6

초록

The expected increase in renewable energy sources (RESs) and electric vehicles (EVs) connected to distribution systems will result in many technical constraints. A meshed network is a promising solution; however, some remarkable challenges must be overcome. Among these, this paper mainly focuses on the line overload and short circuit current of a networked distribution system (NDS) in Korea, an advanced form of meshed network. An NDS refers to a system in which there exists permanent linkages between four feeders and N x N communication-based protection. We propose a method, which employs the tap changing control algorithm of the series reactor to control line overload and short circuit current. MATLAB/Simulink was used to evaluate the proposed method. Three different types of distribution system were employed. First, the utilization rate and feeder imbalance were analyzed in steady-state condition. Subsequently, the short circuit current was analyzed in short circuit condition. The results revealed that the proposed method can effectively prevent line overload in up to 82.7% of cases, enhance the utilization rate by up to 79.9%, and relieve the short circuit current; that is, it can contribute to system stability and the economic operation of an NDS.

키워드

meshed network; radial distribution system (RDS); networked distribution system (NDS); series reactor; utilization rate; feeder imbalance; short circuit current; MESHED DISTRIBUTION NETWORK; HOSTING CAPACITY
제목
Control Strategy for Line Overload and Short Circuit Current of Networked Distribution Systems
저자
Lee, Junwoo; Chae, Wookyu; Kim, Woohyun; Choi, Sungyun
DOI
10.3390/su14074208
발행일
2022-04
유형
Article
저널명
Sustainability
권
14
호
7