Performance comparison among two-phase, liquid, and vapor injection heat pumps with a scroll compressor using R410A

Citations

WEB OF SCIENCE

90
Citations

SCOPUS

93

초록

Although two-phase injection technique is expected to improve the performance and reliability of heat pumps in cold climate conditions, its application is limited due to wet-compression. In this study, a numerical model was developed and validated to predict the performance of liquid, vapor, and two-phase injection heat pumps. The performance characteristics of the liquid, vapor, and two-phase injection heat pumps with a scroll compressor using R410A were compared with the others, based on the predicted data. The optimum injection quality in the two-phase injection heat pump to achieve maximum COP was analyzed as a function of the injection pressure, compressor frequency, and outdoor temperature. The two-phase injection heat pump with the optimum injection quality exhibited the highest COP among all injection types with a proper discharge temperature. In addition, the two-phase injection heat pump with the optimum injection quality was more effective in COP improvement with decreasing outdoor temperature.

키워드

Two-phase injection; Vapor injection; Liquid injection; Heat pump; Scroll compressor; REFRIGERANT INJECTION; ELECTRIC VEHICLES; SYSTEMS; OPTIMIZATION; COLD; R32; TEMPERATURE; GEOMETRIES
제목
Performance comparison among two-phase, liquid, and vapor injection heat pumps with a scroll compressor using R410A
저자
Kim, Dongwoo; Jeon, Yongseok; Jang, Dong Soo; Kim, Yongchan
DOI
10.1016/j.applthermaleng.2018.03.086
발행일
2018-06-05
유형
Article
저널명
Applied Thermal Engineering
권
137
페이지
193 ~ 202