A new methodology for identification of critical lines using damping sensitivity analysis

Citations

WEB OF SCIENCE

2
Citations

SCOPUS

2

초록

When an inter-area mode dominates a low-frequency oscillation in a stressed condition, control of the active power flow of interface lines, with compensating devices, can effectively reduce the electromechanical power oscillations. In general, interface lines in which inter-area oscillations are large are considered to be good locations for installation of compensating devices. A sensitivity analysis with respect to change in active power flow can provide an important factor in electric power system operation. This paper proposes a new methodology to calculate the damping sensitivity with respect to change in active power flow, which can be useful for accurate selection of critical lines from the viewpoint of small-signal stability. In the proposed methodology. a damping sensitivity index is used to select the critical lines to damp power system oscillations. This paper describes how to derive the damping sensitivity for the selected mode and illustrates an example applying the proposed algorithm to a simple two-area system and the New England 39-bus test system. (C) 2008 Elsevier B.V. All rights reserved.

키워드

Inter-area oscillationEigenvalue analysisDamping sensitivityIdentification of critical linesSmall-signal stabilityMULTIMACHINE POWER-SYSTEMSFACTS-BASED STABILIZERSELECTROMECHANICAL OSCILLATIONSLOCATIONSCOMPENSATORSPREDICTIONSIGNALSDEVICESDESIGN
제목
A new methodology for identification of critical lines using damping sensitivity analysis
저자
Cho, Yoon-SungSong, HwachangJang, Gilsoo
DOI
10.1016/j.epsr.2008.08.006
발행일
2009-04
유형
Article
저널명
Electric Power Systems Research
79
4
페이지
562 ~ 568