Protective relay system for the first demonstration of the HTS cable and the SFCL in live grid in Korea

  • Lee, Seung Ryul
  • Yoon, Jaeyoung
  • Yang, Byeong-mo
  • Lee, Byongjun
Citations

WEB OF SCIENCE

2
Citations

SCOPUS

3

초록

This study proposed a novel power protection system for the application of 22.9 kV HTS cable and SFCL systems to the Icheon substation in South Korea, and studied the protective coordination of the proposed system using a transient simulation program, PSCAD/EMTDC. Korea Electric Power Cooperation (KEPCO) designed and reconstructed the protection system of the Icheon substation based on the results of this study. The 22.9 kV, 50 MVA HTS cable and 22.9 kV, 630 A hybrid SFCL systems have been successfully operated in the live power grid of the Icheon substation since August, 2011. (C) 2013 Elsevier B.V. All rights reserved.

키워드

HTS cableSFCLProtection systemProtective relayPower system
제목
Protective relay system for the first demonstration of the HTS cable and the SFCL in live grid in Korea
저자
Lee, Seung RyulYoon, JaeyoungYang, Byeong-moLee, Byongjun
DOI
10.1016/j.physc.2013.04.026
발행일
2013-11
유형
Article
저널명
Physica C: Superconductivity and its Applications
494
페이지