When an FITS coated conductor (CC) is used as a conductor of a superconducting fault current limiter (SFCL), the CC is expected to be exposed to the over-current and temperature of the CC is expected to be increased rapidly by electrical joule heating. Because the CC is a composite tape, thermal and electrical properties of composite materials could affects over-current limiting capacity and recovery time of SFCL This paper presents experimental and numerical results of over-current test and recovery time measurement test on four bifilar wound SFCL modules. The temperature transitions of the samples were estimated from total electrical resistance of the coils. We fabricated one bifilar solenoid coil and three bifilar pancake coils whose cryogenic conditions were different from the other coils. An numerical model was also fabricated to simulate the temperature transition and the numerical results were compared with experimental results. (C) 2010 Elsevier Ltd. All rights reserved.