Impact of Short Circuit Ratio on Harmonic Distortion in Offshore Wind Farm Integration

  • Lee, Kiryeon; 
  • Yoon, Myungseok; 
  • Lee, Jonghyun; 
  • Gham, Seungjun; 
  • Choi, Sungyun
Citations

WEB OF SCIENCE

1
Citations

SCOPUS

1

초록

Offshore wind energy is rapidly expanding as a critical resource for global carbon neutrality, with 10.8 GW of new capacity added in 2023, raising the worldwide total to 75.2 GW. However, large-scale integration of offshore wind farms introduces power quality challenges due to the characteristics of inverter-based resources, particularly harmonic distortion, which can threaten system stability. This study quantitatively investigates the influence of short circuit ratio (SCR) on voltage and current harmonic distortion during offshore wind farm integration. A 500 MW offshore wind farm was modeled, and MATLAB/Simulink simulations were performed for 345 kV and 154 kV systems to evaluate the impact of varying SCR on total harmonic distortion (THD) and individual harmonic orders. Furthermore, the harmonic assessment based on the IEC 61400-21-2 summation method was compared with the simulation results, demonstrating the limitations of the simple summation approach and underscoring the importance of simulation-based evaluation. The results reveal that, under certain SCR conditions, parallel resonance caused by system impedance and line parameters produces unexpectedly high distortion in the 345 kV system, contrary to expectations based solely on voltage level. This resonance phenomenon and SCR dependency were also validated using short circuit capacity data from actual offshore wind farm candidate sites. Overall, the study emphasizes the necessity of comprehensive power quality assessments that account for SCR conditions, voltage levels, and harmonic emission characteristics, providing practical guidance for site selection, substation design, and harmonic mitigation in offshore wind integration.

키워드

offshore wind farm; harmonic distortion; short circuit ratio (SCR); voltage total harmonic distortion (THD); power quality; POWER
제목
Impact of Short Circuit Ratio on Harmonic Distortion in Offshore Wind Farm Integration
저자
Lee, Kiryeon; Yoon, Myungseok; Lee, Jonghyun; Gham, Seungjun; Choi, Sungyun
DOI
10.3390/en18205480
발행일
2025-10-17
유형
Article
저널명
Energies
권
18
호
20