Analysis of thermal environment and energy performance by biased economizer outdoor air temperature sensor fault

  • Kim, Chul Ho
  • Lee, Sung Chan
  • Park, Kyung Soon
  • Lee, Kwang Ho
Citations

WEB OF SCIENCE

8
Citations

SCOPUS

9

초록

In order to develop a fault detection and diagnosis (FDD) algorithm for air handling unit (AHU) based on machine learning, the economizer outdodor air temperature (OAT) sensor fault was modeled. Through EnergyPlus program, the economizer OAT sensor modeled a fault that measures the OAT that's higher or lower than the actual temperature. The distribution of abnormal node point air temperature produced by the fault at the control point of the economizer was reviewed. In addition, the relationship between OAT & mixed air temperature (MAT), OAT & outdoor air fraction (OAF), AHU cooling coil energy, and chiller energy were comparatively analyzed for each fault model. In the case of the fault models, although outdoor air suitable for cooling could be utilized during the operation, outdoor air was not introduced for cooling, and in the opposite case, outdoor air was introduced even when OAT was higher than the indoor set-point temperature, reducing the energy saving effect for cooling. In the future, we aim to analyze energy performance and indoor air quality according to the fault in the return air temperature (RAT) sensor and error in the opening position of the damper. In addition, we plan to continue the analysis of fault data for the various elements of an AHU, and develop FDD algorithms using machine learning.

키워드

EconomizerFault detection diagnosisMachine learningEnergyPlusOutdoor air temperature sensor
제목
Analysis of thermal environment and energy performance by biased economizer outdoor air temperature sensor fault
저자
Kim, Chul HoLee, Sung ChanPark, Kyung SoonLee, Kwang Ho
DOI
10.1007/s12206-022-0342-0
발행일
2022-04
유형
Article
저널명
Journal of Mechanical Science and Technology
36
4
페이지
2083 ~ 2094