Strategy to Enhance Emergency Interconnected Operation of Water Distribution System

Citations

WEB OF SCIENCE

3
Citations

SCOPUS

4

초록

This study identified the causes of insufficient emergency interconnected operation (EIO) performance, such as pressure-related problems and connection problems caused by elevation differences between blocks, the characteristics and locations of emergency interconnection pipes (EIPs), and pumps. Then, it tested four strategies to improve the EIO performance, including increasing the EIP diameter or installing additional EIPs, pressure reducing valves (PRVs), or pumps. The advanced pressure-driven analysis model was applied to quantify the EIO performance improvement achieved using these strategies. Further, these strategies were tested in a real water distribution system. To solve the low-pressure problem, the EIP diameter was increased and an additional pump was installed; the former did not significantly improve, whereas the latter improved supply by 20-30%. To solve the high-pressure problem, PRVs were installed to maintain the EIO performance effectively. To solve connection problems, new EIPs were installed. Although this improved the supply performance, the installation of pumps was recommended to overcome elevation differences. The proposed strategies should contribute to the allocation of facilities such as EIPs, pumps, and PRVs for realizing effective EIO.

키워드

emergency interconnected operationwater distribution systememergency interconnection piperesiliencedisaster managementadvanced pressure-driven analysisPIPE BURSTSRELIABILITYDESIGNENTROPYEVENTSCOST
제목
Strategy to Enhance Emergency Interconnected Operation of Water Distribution System
저자
Jun, HwandonGim, ArinJung, DonghwiLee, Seungyub
DOI
10.3390/su14105804
발행일
2022-05
유형
Article
저널명
Sustainability
14
10