Real Time Wide Area Voltage Stability Index in the Korean Metropolitan Area

Citations

WEB OF SCIENCE

9
Citations

SCOPUS

13

초록

Through the development of phasor measurement units (PMU), various aspects of power system dynamic behavior could be monitored and diagnosed. Monitoring dynamic voltage stability has become one of the achievements we can obtain from PMUs. It is very important to select the most appropriate method for the Korea Electric Power Corporation (KEPCO) system since there are many voltage stability indices In this paper, we propose an advanced WAVI (Wide Area Voltage Stability) that is Well Suited for the purposes of monitoring the dynamic voltage stability of KEPCO's PMU installation plan. The salient features of the proposed index are i) it uses only PMU measurements without coupling with EMS data; ii) it is computationally unburdened and can be applied to real-time situations. The proposed index is applied to the KEPCO test system and the results show that it successfully predicts voltage instability through comparative studies.

키워드

Wide Area Voltage stability Index; Synchro-Phase; Phasor Measurement Unit
제목
Real Time Wide Area Voltage Stability Index in the Korean Metropolitan Area
저자
Han, Sangwook; Lee, Byongjun; Kim, Sangtae; Moon, Younghwan
발행일
2009-12
유형
Article
저널명
Journal of Electrical Engineering & Technology
권
4
호
4
페이지
451 ~ 456