A study of the application of fast valving and braking resistor for an intelligent SPS

Citations

WEB OF SCIENCE

8
Citations

SCOPUS

10

초록

There are some kinds of remedial action schemes that deal with sudden disturbance situations in a transmission network. Generator tripping with an SPS (Special Protection System) is one of the remedial action schemes, and it is a powerful and effective method of solving transient stability problems. When an extra-high-voltage transmission line that is transferring a large amount of power is tripped, generators designated by a SPS are tripped to prevent over-speeding of the generators. However, the tripping of generators can cause difficulties in the power system operation, and if large amounts of power are tripped, load shedding can occur. Therefore, it is desirable that a minimum number of generators is tripped in required stable conditions. For this purpose, an intelligent SPS is currently being developed to reduce the number of generator tripping events. In this paper, an application method involving fast valving and a braking resistor are analyzed as suitable action schemes for a SPS. (C) 2013 Elsevier Ltd. All rights reserved.

키워드

Intelligent SPSTransient stabilityFast valvingBraking resistorGenerator tripping
제목
A study of the application of fast valving and braking resistor for an intelligent SPS
저자
Yoon, Dong-HeeJang, GilsooMoon, Young-Hwan
DOI
10.1016/j.ijepes.2013.05.049
발행일
2013-12
유형
Article
저널명
International Journal of Electrical Power and Energy Systems
53
페이지