Fault analysis in the grid with inverter-based distributed generation considering the interconnection transformer topology

  • Yoon, M.
  • Lee, M.
  • Cho, N.
  • Choi, S.
Citations

SCOPUS

2

초록

For conducting the fault analysis in a system with distributed generation, the sequence equivalent circuit is used. Due to the characteristics of distributed generation that reverse currents occur, the size of the fault current can be determined by the path where fault current can flow into the fault point in the negative sequence and zero sequence. In this paper, we calculate and compare the fault currents in the system with inverter-based distributed generation considering the topology of transformer winding. From the results, we can analyze the effect of the interconnection transformer in the fault analysis. Copyright © The Korean Institute of Electrical Engineers.

키워드

Distributed generationFault analysisFault currentInterconnection transformer
제목
Fault analysis in the grid with inverter-based distributed generation considering the interconnection transformer topology
저자
Yoon, M.Lee, M.Cho, N.Choi, S.
DOI
10.5370/KIEE.2021.70.9.1274
발행일
2021
유형
Article
저널명
전기학회논문지
70
9
페이지
1274 ~ 1281