상세 보기
Effects of ejector geometries on performance of ejector-expansion R410A air conditioner considering cooling seasonal performance factor
- Jeon, Yongseok;
- Jung, Jongho;
- Kim, Dongwoo;
- Kim, Sunjae;
- Kim, Yongchan
WEB OF SCIENCE
45SCOPUS
48초록
The objective of this study was to investigate the effects of ejector geometries on the performance of an ejector expansion air conditioner (EEAC) considering the cooling seasonal performance factor (CSPF). The performance of the EEAC using R410A was measured and analyzed by varying the compressor speed, outdoor-bin temperature, operating pressures, nozzle-throat diameter, and mixing-section diameter. The EEAC in the medium capacity mode exhibited maximum coefficient of performance (COP) improvement, i.e., 7.5%, over the baseline (conventional) cycle. The optimum mixing-section diameter was determined to be 9 mm based on the CSPF. In addition, the optimum mixing-section diameter increased with an increase in the annual average outdoor temperature. The CSPF of the EEAC with the optimized mixing-section diameter improved in the range of 16.0-20.3% over the baseline cycle depending on the climatic conditions.
키워드
- 제목
- Effects of ejector geometries on performance of ejector-expansion R410A air conditioner considering cooling seasonal performance factor
- 저자
- Jeon, Yongseok; Jung, Jongho; Kim, Dongwoo; Kim, Sunjae; Kim, Yongchan
- 발행일
- 2017-11-01
- 유형
- Article
- 저널명
- Applied Energy
- 권
- 205
- 페이지
- 761 ~ 768
- 언어
- ENG
- 출판사
- ELSEVIER SCI LTD
- 발행국가
- 영국
- 분량
- 8 페이지
- ISSN
- E 1872-9118
P 0306-2619