Effects of flash tank vapor injection on the heating performance of an inverter-driven heat pump for cold regions

Citations

WEB OF SCIENCE

101
Citations

SCOPUS

128

초록

A heat pump has received much attention as substitute for the conventional boiler or heating coil because of its high efficiency. For the wide application of the heat pump, the most important design factor is the performance degradation upon its installation in tropical and cold regions. In this study, the effects of flash tank vapor injection on the heating performance of a two-stage heat pump with an inverter-driven twin rotary compressor were measured and analyzed for compressor frequency ranging from 50 to 100 Hz at ambient temperatures of -15, -5, and 5 degrees C. The COP and heating capacity of the injection cycle were enhanced by 10% and 25%, respectively, at the ambient temperature of -15 C. The total mass flow rate of the injection cycle was 30-38% higher than that of the non-injection cycle. (C) 2010 Elsevier Ltd and IIR. All rights reserved.

키워드

Heat pumpTwo-stage systemVariable speedCompressorExperimentInjectionPerformanceCOPSCROLL COMPRESSORSYSTEM
제목
Effects of flash tank vapor injection on the heating performance of an inverter-driven heat pump for cold regions
저자
Heo, JaehyeokJeong, Min WooKim, Yongchan
DOI
10.1016/j.ijrefrig.2009.12.021
발행일
2010-06
유형
Article
저널명
International Journal of Refrigeration
33
4
페이지
848 ~ 855