Analysis of two-phase injection heat pump using artificial neural network considering APF and LCCP under various weather conditions

Citations

WEB OF SCIENCE

20
Citations

SCOPUS

19

초록

The objective of this study is to optimize the performance of a two-phase injection (TPI) heat pump considering annual performance factor (APF) and life cycle climate performance (LCCP). The performances of non-injection (NI), vapor injection (VI), and TPI heat pumps are measured under various outdoor temperatures. Based on the measured data, artificial neural network models for the NI, VI, and TPI heat pumps are developed to predict the performance indexes during cooling and heating seasons. As a result, the TPI heat pump shows higher heating capacity than the NI and VI heat pumps with a lower compressor discharge temperature in cold weather conditions. Therefore, the application of the TPI has a merit on reducing the size of the heat pump due to its lower back-up heater loss and over-capacity penalty. When the objective function maximizes the APF for system optimization in three climate regions, the TPI heat pump shows a 1.4-2.7% higher APF than the NI heat pump, and a 11.1%-18.1% smaller optimum rated heating capacity. (C) 2018 Elsevier Ltd. All rights reserved.

키워드

Two-phase injection; Optimization; Annual performance; LCCP; Artificial neural network; SCROLL COMPRESSOR; VAPOR INJECTION; WIND TURBINE; PERFORMANCE EVALUATION; REFRIGERANT INJECTION; SYSTEMS; INTELLIGENT; STRATEGY; CYCLE; R32
제목
Analysis of two-phase injection heat pump using artificial neural network considering APF and LCCP under various weather conditions
저자
Kim, Dongwoo; Song, Kang Sub; Lim, Junyub; Kim, Yongchan
DOI
10.1016/j.energy.2018.05.046
발행일
2018-07-15
유형
Article
저널명
Energy
권
155
페이지
117 ~ 127