상세 보기
초록
The leakage rate of air from a fume hood is an important factor for calculating the internal exposure at a workplace using the dose conversion factors recommended by the International Atomic Energy Agency. In this study, the leakage rate from a fume hood was estimated in a radioisotope laboratory using computational fluid dynamics simulations. For this purpose, a three-dimensional fume hood model was built using CAD software. In this model, the leakage rate was calculated to be 3%, with face velocities between 0.1 and 1.0 m/s at the sash opening of the fume hood. This rate rapidly decreased to zero as the face velocities decreased to less than 0.1 m/s.
키워드
Internal exposure; Dose calculation; Dose conversion factor; Back flow; Fume hood; Hot lab; PERFORMANCE; FLOW
- 제목
- Estimation of leakage rate of air from a fume hood in a radioisotope laboratory using CFD simulations
- 저자
- Kim, Sangrok; Yang, Hyungjin
- 발행일
- 2018-10
- 유형
- Article
- 권
- 140
- 페이지
- 300 ~ 304