운전조건 변화에 따른 이산화탄소 열펌프의 냉난방 성능특성 비교

Cooling and Heating Performances of a CO₂ Heat Pump with the Variations of Operating Conditions

초록

Since operating conditions are significantly different for heating and cooling mode operations in a CO₂ heat pump system, it is difficult to optimize the performance of the CO₂ cycle. In addition, the performance of a CO₂ heat pump is very sensitive to outdoor temperature and gascooler pressure. In this study, the cooling and heating performances of a variable speed CO₂ heat pump with a twin-rotary compressor were measured and analyzed with the variations of EEV opening and compressor frequency. As a result, the cooling and heating COPs were 2.3 and 3.0, respectively, when the EEV opening was 22%. When the optimal EEV openings for heating and cooling were 28% and 16%, the cooling and heating COPs increased by 3.3% and 3.9%, respectively, over the COPs at the EEV opening of 22%. Beside, the heating performance was more sensitive to EEV opening than the cooling performance. As the compressor speed decreased by 5 Hz, the cooling COP increased by 2%, while the heating COP decreased by 8%.

키워드

Carbon Dioxide(이산화탄소)Transcritical Cycle(초월임계 사이클)Coefficient of Performance(COP성능계수)Electronic Expansion Valve(EEV전자팽창밸브)
제목
운전조건 변화에 따른 이산화탄소 열펌프의 냉난방 성능특성 비교
제목 (타언어)
Cooling and Heating Performances of a CO₂ Heat Pump with the Variations of Operating Conditions
저자
김용찬조홍현백창현이응찬강훈
발행일
2008
저널명
대한기계학회논문집 B
32
6
페이지
454 ~ 462