상세 보기
운전조건 변화에 따른 이산화탄소 열펌프의 냉난방 성능특성 비교
- 김용찬;
- 조홍현;
- 백창현;
- 이응찬;
- 강훈
초록
Since operating conditions are significantly different for heating and cooling mode operations in a CO₂ heat pump system, it is difficult to optimize the performance of the CO₂ cycle. In addition, the performance of a CO₂ heat pump is very sensitive to outdoor temperature and gascooler pressure. In this study, the cooling and heating performances of a variable speed CO₂ heat pump with a twin-rotary compressor were measured and analyzed with the variations of EEV opening and compressor frequency. As a result, the cooling and heating COPs were 2.3 and 3.0, respectively, when the EEV opening was 22%. When the optimal EEV openings for heating and cooling were 28% and 16%, the cooling and heating COPs increased by 3.3% and 3.9%, respectively, over the COPs at the EEV opening of 22%. Beside, the heating performance was more sensitive to EEV opening than the cooling performance. As the compressor speed decreased by 5 Hz, the cooling COP increased by 2%, while the heating COP decreased by 8%.
키워드
- 제목
- 운전조건 변화에 따른 이산화탄소 열펌프의 냉난방 성능특성 비교
- 제목 (타언어)
- Cooling and Heating Performances of a CO₂ Heat Pump with the Variations of Operating Conditions
- 저자
- 김용찬; 조홍현; 백창현; 이응찬; 강훈
- 발행일
- 2008
- 저널명
- 대한기계학회논문집 B
- 권
- 32
- 호
- 6
- 페이지
- 454 ~ 462