판형 열교환기에서 에틸렐글리콜 수용액의 열전달 및 압력강하 특성에 관한 실험적 연구

An Experimental Study on the Heat-Transfer and Pressure-Drop Characteristics of Ethylene-Glycol Water in a Plate Heat Exchanger
  • 정현준; 
  • 강훈; 
  • 김용찬; 
  • 이광진; 
  • 이동균; 
  • 외 2명

초록

Having desirable thermal characteristics, such as a low freezing point, a high boiling point, better stability over a wide range of temperatures, and good thermophysical properties, ethylene-glycol water is a very popular antifreeze and heat-transfer fluid in numerous commercial and industrial applications. In this study, the heat-transfer and pressure-drop characteristics of a brazed-plate heat exchanger were investigated experimentally using ethylene-glycol water and R410a as the two fluids in a plate heat exchanger. The heat-transfer rate and pressure drop of the ethylene-glycol water were measured by changing inlet temperature, volumetric flow rate, and composition. The inlet temperature, volumetric flow rate, and composition were varied from 12.0 to 30.0℃, 4.9 to 26.8 lpm, and 30 to 55 percent, respectively. In addition, correlations were proposed to predict the heat-transfer coefficient and friction factor.

키워드

Ethylene-glycol water(에틸렌 글리콜 수용액); Heat transfer(열전달); Plate heat exchanger(판형 열교환기); Pressure drop(압력강하)
제목
판형 열교환기에서 에틸렐글리콜 수용액의 열전달 및 압력강하 특성에 관한 실험적 연구
제목 (타언어)
An Experimental Study on the Heat-Transfer and Pressure-Drop Characteristics of Ethylene-Glycol Water in a Plate Heat Exchanger
저자
정현준; 강훈; 김용찬; 이광진; 이동균; 이원희; 신완순
DOI
10.6110/KJACR.2018.30.8.358
발행일
2018
저널명
설비공학 논문집
권
30
호
8
페이지
358 ~ 365