이산화탄소 급탕 열펌프의 운전조건에 따른 성능 특성에 관한 실험적 연구

Experimental Study on the Performance of a CO_2 Heat Pump Water Heater under Various Operating Conditions
  • 손동진
  • 백창현
  • 허재혁
  • 강훈
  • 김용찬

초록

In this study, the steady state performance of a CO_2 heat pump water heater was measured with a variation of operating conditions such as refrigerant charge amount, compressor frequency, EEV opening, and water mass flow rate. Transient state performance tests were also conducted to investigate major system effects associated with the interaction between the CO_2 heat pump water heater and the water tank. Optimum refrigerant charge amount for the system was 1600 g. At compressor frequencies of 50 Hz and 60 Hz, water mass flow rates of 95 kg/h and 105 kg/h, and EEV opening of 8% and 16%, the water heating temperatures were 65℃ and 68℃ and COPs were 3.0 and 2.8, respectively. In the transient condition, the instantaneous COP decreased with an increase in the inlet water temperature.

키워드

CO_2 heat pump water heater(이산화탄소 급탕 열펌프)Water heating temperature (급탕온도)Coefficient of Performance(COP성능계수)
제목
이산화탄소 급탕 열펌프의 운전조건에 따른 성능 특성에 관한 실험적 연구
제목 (타언어)
Experimental Study on the Performance of a CO_2 Heat Pump Water Heater under Various Operating Conditions
저자
손동진백창현허재혁강훈김용찬
발행일
2011
저널명
설비공학 논문집
23
4
페이지
273 ~ 280