Back-analyses of in-situ thermal response test (TRT) for evaluating ground thermal conductivity

Authors
Lee, C.Park, M.Park, S.Won, J.Choi, H.
Issue Date
9월-2013
Publisher
WILEY
Keywords
closed-loop vertical ground heat exchanger; thermal response test; back-analysis; computational fluid dynamics; effective thermal conductivity
Citation
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, v.37, no.11, pp.1397 - 1404
Indexed
SCIE
SCOPUS
Journal Title
INTERNATIONAL JOURNAL OF ENERGY RESEARCH
Volume
37
Number
11
Start Page
1397
End Page
1404
URI
https://scholar.korea.ac.kr/handle/2021.sw.korea/102387
DOI
10.1002/er.2929
ISSN
0363-907X
Abstract
In this study, a series of computational fluid dynamics (CFD) numerical analyses was performed in order to evaluate the performance of six full-scale closed-loop vertical ground heat exchangers constructed in a test bed located in Wonju, South Korea. The high-density polyethylene pipe, borehole grouting and surrounding ground formation were modeled using FLUENT, a finite-volume method program, for analyzing the heat transfer process of the system. Two user-defined functions accounting for the difference in the temperatures of the circulating inflow and outflow fluid and the variation of the surrounding ground temperature with depth were adopted in the FLUENT model. The relevant thermal properties of materials measured in laboratory were used in the numerical analyses to compare the thermal efficiency of various types of the heat exchangers installed in the test bed. The numerical simulations provide verification for the in-situ thermal response test (TRT) results. The numerical analysis with the ground thermal conductivity of 4.0 W/mK yielded by the back-analysis was in better agreement with the in-situ TRT result than with the ground thermal conductivity of 3.0 W/mK. From the results of CFD back-analyses, the effective thermal conductivities estimated from both the in-situ TRT and numerical analysis are smaller than the ground thermal conductivity (=4.0 W/m.K) that is input in the numerical model because of the intrinsic limitation of the line source model that simplifies a borehole assemblage as an infinitely long line source in the homogeneous material. However, the discrepancy between the ground thermal conductivity and the effective thermal conductivity from the in-situ TRT decreases when borehole resistance decreases with a new three pipe-type heat exchanger leads to less thermal interference between the inlet and outlet pipes than the conventional U-loop type heat exchanger. Copyright (c) 2012 John Wiley & Sons, Ltd.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > School of Civil, Environmental and Architectural Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher CHOI, HANG SEOK photo

CHOI, HANG SEOK
공과대학 (건축사회환경공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE