The cooling seasonal performance factor of a hybrid ground-source heat pump with parallel and serial configurations
- Authors
- Park, Honghee; Lee, Joo Seoung; Kim, Wonuk; Kim, Yongchan
- Issue Date
- 2월-2013
- Publisher
- ELSEVIER SCI LTD
- Keywords
- Hybrid ground-source heat pump; Cooling seasonal performance factor; Configuration; COP; Heat rejection ratio; Ground thermal degradation
- Citation
- APPLIED ENERGY, v.102, pp.877 - 884
- Indexed
- SCIE
SCOPUS
- Journal Title
- APPLIED ENERGY
- Volume
- 102
- Start Page
- 877
- End Page
- 884
- URI
- https://scholar.korea.ac.kr/handle/2021.sw.korea/104084
- DOI
- 10.1016/j.apenergy.2012.09.035
- ISSN
- 0306-2619
- Abstract
- A hybrid ground-source heat pump (HGSHP) is proposed to overcome the decrease in the performance of a ground-source heat pump (GSHP) at the degraded ground thermal condition. In this study, a performance comparison between the GSHP and the HGSHP with parallel and serial configurations was conducted by varying the leaving fluid temperature (LFT) of the ground heat exchanger (GHEX), the fluid flow rate of the supplemental loop, the mean outdoor bin temperature, and the switching temperature of the hybrid operation. At the LFT of the GHEX of 40 degrees C, the coefficient of performances (COPS) for the HGSHP with the parallel and serial configurations were 18% and 6% higher than that of the GSHP, respectively. The cooling seasonal performance factors (CSPFs) of the HGSHPs with the parallel and the serial configurations were 6.5% and 2.0% higher, respectively, than that of the GSHP for Daegu city in South Korea. (c) 2012 Elsevier Ltd. All rights reserved.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - College of Engineering > Department of Mechanical Engineering > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.