네트워크 부하 조건의 변화가 채널 상태 정보에 미치는 영향을 고려한 옥내 전력선 통신 채널의 채널 용량 분석Channel Capacity Analysis for Indoor PLC Networks with Considering the Effect of Loading conditions of Networks on Channel State Information
- Other Titles
- Channel Capacity Analysis for Indoor PLC Networks with Considering the Effect of Loading conditions of Networks on Channel State Information
- Authors
- 신재영; 정지채
- Issue Date
- 2011
- Publisher
- 대한전기학회
- Keywords
- Channel capacity; Channel state information; PLC; Power-line communications
- Citation
- 전기학회논문지, v.60, no.2, pp.252 - 256
- Indexed
- SCOPUS
KCI
- Journal Title
- 전기학회논문지
- Volume
- 60
- Number
- 2
- Start Page
- 252
- End Page
- 256
- URI
- https://scholar.korea.ac.kr/handle/2021.sw.korea/114454
- ISSN
- 1975-8359
- Abstract
- We analyze the channel capacity with considering the effect of the loading conditions of indoor PLC networks on channel state information. We consider various numbers of load for two kinds of the networks with regular length branches and a deployed network of indoor PLC. For calculating the channel capacity degradation, two noise scenarios and impedances are considered. From the simulation results, we suggest the robust regression lines for modeling the channel capacity degradation. In the cases of 0 Ω and Z0loads, natural log and linear function curve show the best goodness of fit, respectively. For the deployed indoor PLC network with 0 Ω loads, compared with the networks with regular length branches, the goodness of fit decreases by the amount of 0.12 and 0.15 for low noise and high noise scenarios, respectively. Using the regression lines, we can estimate the channel capacity degradation without measurement.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - Graduate School > Department of Brain and Cognitive Engineering > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.