지중 순환수 유량 변화에 따른 지열원 히트펌프 시스템의 성능 특성 연구Influence of the Secondary Fluid Flow Rate on the Performance of a GSHP System
- Other Titles
- Influence of the Secondary Fluid Flow Rate on the Performance of a GSHP System
- Authors
- 이준엽; 정진택; 우정선; 최종민
- Issue Date
- 2010
- Publisher
- 대한설비공학회
- Keywords
- GSHP(지열원 히트펌프 시스템); GLHX(지중 열교환기); COP(성능계수); Flow rate(유량); Load(부하)
- Citation
- 설비공학 논문집, v.22, no.10, pp.649 - 656
- Indexed
- KCI
- Journal Title
- 설비공학 논문집
- Volume
- 22
- Number
- 10
- Start Page
- 649
- End Page
- 656
- URI
- https://scholar.korea.ac.kr/handle/2021.sw.korea/118490
- ISSN
- 1229-6422
- Abstract
- The aim of this study is to investigate the influence of the secondary fluid flow rate through GLHX on a GSHP system with vertical single U-tube type GLHXs. The COP of a GSHP system with large flow rate was lower than it with small flow rate due to large power consumption of ground loop circulating pump. It is suggested that the heat pump unit with high COP and low flow rate through the GLHX have to be selected in order to enhance the performance of the system and reduce the length of GLHX.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - College of Engineering > Department of Mechanical Engineering > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.