Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Effects of Gas Injection on the Heating Performance of a Two-Stage Heat Pump Using a Twin Rotary Compressor with Refrigerant Charge AmountEffects of Gas Injection on the Heating Performance of a Two-Stage Heat Pump Using a Twin Rotary Compressor with Refrigerant Charge Amount

Other Titles
Effects of Gas Injection on the Heating Performance of a Two-Stage Heat Pump Using a Twin Rotary Compressor with Refrigerant Charge Amount
Authors
허재혁정민우전종욱김용찬
Issue Date
2008
Publisher
대한설비공학회
Keywords
Gas Injection; Two-Stage Cycle; R-410A; Refrigerant Charge; Heat Pump; Gas Injection; Two-Stage Cycle; R-410A; Refrigerant Charge; Heat Pump
Citation
International Journal of Air-Conditioning and Refrigeration, v.16, no.3, pp.77 - 82
Indexed
KCI
OTHER
Journal Title
International Journal of Air-Conditioning and Refrigeration
Volume
16
Number
3
Start Page
77
End Page
82
URI
https://scholar.korea.ac.kr/handle/2021.sw.korea/124854
ISSN
2010-1325
Abstract
For heat pumps used in a cold region, it is very important to obtain appropriate heating capacity. Several studies using a variable speed compressor and an additional heater have been performed to enhance heating capacity at low ambient temperatures. However, for outdoor temperature conditions below -15oC, it is still difficult to obtain enough heating capacity above the rated value. In recent studies, the application of gas injection technique into a two-stage heat pump yielded noticeable heating performance improvement at low temperature conditions. In this study, the heating performance of a two-stage gas injection heat pump with a rated capacity of 3.5 kW was measured and ana-lyzed by varying refrigerant charge amount and EEV opening at the standard heating condition. The heating performance of the two-stage gas injection heat pump was compared with that of a two-stage non-injection heat pump. The heating capacity and COP of the two-stage gas injection heat pump were improved by 2-10% at the optimal charging condition over those of the two-stage non-injection heat pump.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > Department of Mechanical Engineering > 1. Journal Articles