Analysis on Thermal Performance of Ground Heat Exchanger According to Design Type Based on Thermal Response Test

Authors
이광호
Issue Date
2월-2019
Publisher
MDPI
Citation
ENERGIES, v.12, no.4
Indexed
SCIE
SCOPUS
Journal Title
ENERGIES
Volume
12
Number
4
URI
https://scholar.korea.ac.kr/handle/2021.sw.korea/139698
ISSN
19961073
Abstract
A ground source heat pump (GSHP) system has higher performance than air source heat pump system due to the use of more efficient ground heat source. However, the GSHP system performance depends on ground thermal properties and groundwater conditions. There are many studies on the improvement of GSHP system by developing ground heat exchanger (GHX) and heat exchange method. Several studies have suggested methods to improve heat exchange rate for the development of GHX. However, few real-scale experimental studies have quantitatively analyzed their performance using the same ground conditions. Therefore, the objective of this study was to evaluate the thermal performance of various pipe types of GHX by the thermal response test (TRT) under the same field and test conditions. Four kinds of GHX (HDPE type, HDPE-nano type, spiral fin type, and coaxial type) were constructed in the same site. Inlet and outlet temperatures of GHXs and effective thermal conductivity were measured through the TRT. In addition, the borehole thermal resistance was calculated to comparatively analyze the correlation of the heat exchange performance with each GHX. Result of the TRT revealed that averages effective thermal conductivities of HDPE type, HDPE-nano, spiral fin type, and coaxial type GHX were 2.25
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > Department of Architecture > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetrics

Total Views & Downloads

BROWSE