A ground source heat pump (GSHP) system utilizes a relatively stable underground temperature to achieve energy-saving for heating and cooling in buildings. Among various types of GSHP systems, Vertical Closed Loop Ground Source Heat Pump (VGSHP) has received increasing attention due to a variety of advantages such as the potential to be installed in a relatively small space and improved energy efficiency. In this research, in order to improve the system performance of a VGSHP, a VGSHP system coupled with heat storage tank was evaluated. For this purpose, the detailed analysis on the operational behavior of heat storage tank and the variations of heat pump energy performance due to the connection with heat storage tank was performed, and characteristics of heat pump part load ratios (PLRs) and the corresponding energy requirements, compared to chiller and boiler based conventional system, were analyzed in detail, using dynamic energy simulation after comprehensive validation process of heat pump performance curves. The results of this study showed that the VGSHP system coupled with heat storage tank showed an energy saving effect of about 20% for cooling and about 77% for heating compared to the conventional air conditioning system, and an energy saving effect of about 2% for cool
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > Department of Architecture > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetrics

Total Views & Downloads

BROWSE