Performance evaluation of coaxial-type GHEX in GSHP system installed in Korean residential building

Authors
Lee, SeokjaePark, SangwooKang, MinkyuChoi, Hangseok
Issue Date
15-3월-2021
Publisher
ELSEVIER SCIENCE SA
Keywords
Ground heat exchanger (GHEX); Coaxial-type GHEX; Ground source heat pump (GSHP); Thermal response test (TRT); Thermal performance test (TPT)
Citation
ENERGY AND BUILDINGS, v.235
Indexed
SCIE
SCOPUS
Journal Title
ENERGY AND BUILDINGS
Volume
235
URI
https://scholar.korea.ac.kr/handle/2021.sw.korea/49473
DOI
10.1016/j.enbuild.2021.110734
ISSN
0378-7788
Abstract
A coaxial-type ground heat exchanger (GHEX) is a closed-loop GHEX with heat exchange pipes in a borehole, arranged in a concentric tube-in-tube configuration. A coaxial-type GHEX enlarges the heat exchange area and induces turbulent flow more actively than conventional closed-loop GHEXs owing to the annular space formed by outer and inner pipes. Therefore, it improves the thermal performance of conventional GHEXs. Herein, the thermal performance of the coaxial-type GHEX was evaluated, and then compared with that of the closed-loop vertical GHEX. The Ground source heat pump (GSHP) system connected with the coaxial-type GHEXs was designed with the ground loop heat exchanger design program (i.e., GLHE-Pro). In accordance with the design, the GSHP system was constructed in a building basement, with four coaxial-type GHEXs and a closed-loop vertical GHEX for comparison purpose. Then, a series of field experiments (i.e., thermal response tests (TRTs), thermal performance tests (TPTs), short-term heating COP tests, and energy saving tests) were conducted to compare the thermal performance of the coaxial-type GHEXs and the closed-loop vertical GHEX with or without the GSHP system. As a result, the coaxial-type GHEX had 20% and 6.7% better thermal performance in TRT and TPT, respectively, than the closed-loop vertical GHEX. In addition, geothermal energy showed more stable performance with the coaxial-type GHEX in the GSHP system, than with the closed-loop vertical GHEX. (c) 2021 Elsevier B.V. All rights reserved.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > School of Civil, Environmental and Architectural Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher CHOI, HANG SEOK photo

CHOI, HANG SEOK
공과대학 (건축사회환경공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE