Comparative analysis of cooling energy performance between water-cooled VRF and conventional AHU systems in a commercial building

Authors
Seo, ByeongmoYoon, Yeo BeomYu, Byeong HoCho, SoolyeonLee, Kwang Ho
Issue Date
4월-2020
Publisher
PERGAMON-ELSEVIER SCIENCE LTD
Keywords
Variable refrigerant flow (VRF); EnergyPlus; Matlab; BCVTB; Cooling energy; Water-cooled VRF
Citation
APPLIED THERMAL ENGINEERING, v.170
Indexed
SCIE
SCOPUS
Journal Title
APPLIED THERMAL ENGINEERING
Volume
170
URI
https://scholar.korea.ac.kr/handle/2021.sw.korea/56711
DOI
10.1016/j.applthermaleng.2020.114992
ISSN
1359-4311
Abstract
With recent efforts to minimize the energy consumption of heating, ventilation and air conditioning (HVAC) systems in buildings, the variable refrigerant flow heat pump (VRF-HP) system has drawn much attention, replacing the conventional HVAC system in the market. The VRF-HP system has several advantages, such as enhancing the aesthetics of buildings, reducing installation costs and offering high technology products. Although various studies relevant to VRF-HP systems are currently in progress, the evaluation of quantitative energy based on the actual performance information of such systems is still insufficient because it is difficult to accurately reflect various factors affecting their inherent heating and cooling performance in a simulation environment during the design stage. To obtain reliable results for this study, a water-cooled VRF-HP system equipped with a direct expansion air handling unit (DX-AHU) was selected from among various types of VRF-HP systems, and a standardized heating and cooling performance curve in diverse temperatures and part-load conditions based on the heating and cooling field measurement catalog performance data was developed. This paper aims to conduct a comparative assessment of the cooling energy performance between a water-cooled VRF-HP system and a chiller based conventional AHU system through co-simulation between EnergyPlus, MATLAB, and BCVTB after an extensive validation and calibration process. The results indicate that the water-cooled VRF-HP system can reduce cooling energy by up to 15% compared with the chiller based conventional AHU system.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > Department of Architecture > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetrics

Total Views & Downloads

BROWSE