Modeling and Simulation Performance Evaluation of a Proposed Calorimeter for Testing a Heat Pump System
- Authors
- Amoabeng, Kofi Owura; Lee, Kwang Ho; Choi, Jong Min
- Issue Date
- 1-12월-2019
- Publisher
- MDPI
- Keywords
- air handling unit; calorimeter; energy consumption; heat pump; heat recovery unit; test chamber
- Citation
- ENERGIES, v.12, no.23
- Indexed
- SCIE
SCOPUS
- Journal Title
- ENERGIES
- Volume
- 12
- Number
- 23
- URI
- https://scholar.korea.ac.kr/handle/2021.sw.korea/60984
- DOI
- 10.3390/en12234589
- ISSN
- 1996-1073
- Abstract
- The energy consumption for heating and cooling in the building sector accounts for more than one-third of total energy used worldwide. In view of that, it is important to develop energy efficient cooling and heating systems in order to conserve energy in buildings as well as reduce greenhouse gas emissions. In both commercial and residential buildings, the heat pump has been adopted as an energy efficient technology for space heating and cooling purposes as compared to conventional air conditioning systems. However, heat pumps undergo standard testing, rating, and certification procedures to ascertain their system performance. Essentially, the calorimeter for testing heat pumps has two test chambers to serve as a heat source and heat sink to control and maintain the test conditions required to simulate the heat pump indoor and outdoor units, simultaneously. In air-to-air heat pump units, the conventional calorimeter controls the air temperature and humidity conditions in each test chamber with separate air handling units consisting of a refrigerator, heater, humidifier, and supply fan, which results in high energy consumption. In this study, using dynamic modeling and simulation, a new calorimeter for controlling air conditions in each test chamber is proposed. The performance analysis based on simulation results showed that the newly proposed calorimeter predicted at least 43% energy savings with the use of a heat recovery unit and small refrigerator capacity as compared to the conventional calorimeter that utilized a large refrigerator capacity for all the weather conditions and load capacities that we investigated.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - College of Engineering > Department of Architecture > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.