System-Level Vulnerability Analysis for Commutation Failure Mitigation in Multi-infeed HVDC Systems
- Authors
- Yoon, Minhan; Jang, Gilsoo
- Issue Date
- 5월-2018
- Publisher
- KOREAN INST ELECTR ENG
- Keywords
- HVDC; Multi-infeed; LCC; Commutation failure; Power system
- Citation
- JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, v.13, no.3, pp.1052 - 1059
- Indexed
- SCIE
SCOPUS
KCI
- Journal Title
- JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY
- Volume
- 13
- Number
- 3
- Start Page
- 1052
- End Page
- 1059
- URI
- https://scholar.korea.ac.kr/handle/2021.sw.korea/76008
- DOI
- 10.5370/JEET.2018.13.3.1052
- ISSN
- 1975-0102
- Abstract
- This paper deals with commutation failure of the line-commutated converter high voltage direct current (LCC HVDC) system caused by a three phase fault in the ac power system. An analytic calculation method is proposed to estimate the maximum permissible voltage drop at the LCC HVDC station on various operating point and to assess the area of vulnerability for commutation failure (AOV-CF) in the power system based on the residual phase voltage equation. The concept is extended to multi-infeed HVDC power system as the area of severity for simultaneous commutation failure (AOS-CF). In addition, this paper presents the implementation of a shunt compensator applying to the proposed method. An analysis and simulation have been performed with the IEEE 57 bus sample power system and the Jeju island power system in Korea.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - College of Engineering > School of Electrical Engineering > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.